GB50764-2012电厂动力管道设计规范(英文版)
上QQ阅读APP看本书,新人免费读10天
设备和账号都新为新人

5.4 Branch Connection

5.4.1 For the piping with PN≤25,direct connection can be used provided that the reinforcing requirements are met.For piping with PN>25,the branch connection shall adopt tees.

5.4.2 Auxiliary reinforcement in the form of stiffening rings,plates,and ribs should not be used for tees.

5.4.3 Type of tees for main piping may be selected according to Table 5.4.3.

Table 5.4.3 Type of tees for main piping

img

5.4.4 The strength of tees shall meet the reinforcement requirements specified in 6.4 of this code.For stubs,forged tees,and welded tees,area compensation method should be used for determining the strength;for hot extruded tees,the pressure-area method should be used.

5.4.5 The confluence or divergence tees for main steam and reheat steam piping of the units at or above subcritical parameters should be skew tees or"Y"type tees.